4

2F76

...Repeated for module number 15

2FC6

...Repeated for module number 16

3016

...Repeated for module number 17

3066

...Repeated for module number 18

30B6

...Repeated for module number 19

3106

...Repeated for module number 20

3156

...Repeated for module number 21

31A6

...Repeated for module number 22

31F6

...Repeated for module number 23

3246

...Repeated for module number 24

3296

...Repeated for module number 25

32E6

...Repeated for module number 26

3336

...Repeated for module number 27

3386

...Repeated for module number 28

33D6

...Repeated for module number 29

3426

...Repeated for module number 30

SRCx Node Counters (Read/Write) - Write a 0 to these to reset them

3476

Reserved (840 items)

0 to 65535

---

1

F001

0

SRCx Settings (Read/Write)

37BE

SRC X Node Commissioned

0 to 1

---

1

F102

0

37BF

SRC X PT Source Node Identifier

0 to 29

---

1

F001

0

37C0

SRC X Breaker Connection

0 to 1

---

1

F712

0

37C1

Reserved (17 items)

37D2

SRC X PT Rating

0 to 6

---

1

F719

0

37D3

SRC X UV Trip Enable

0 to 1

---

1

F102

0

37D4

SRC X UV Trip Curve Type

0 to 1

---

1

F726

1

37D5

SRC X UV Trip Pickup Setting

10 to 95

%

1

F001

50

37D6

SRC X UV Trip Time Delay

0.5 to 600

S

0.5

F001

30

37D7

SRC X UV Trip Phase Requirement

1 to 3

---

1

F001

1

37D8

SRC X UV Trip Block Volt Enable

0 to 1

---

1

F102

0

37D9

SRC X UV Trip Block Volt Setting

5 to 75

%

1

F001

5

37DA

SRC X UV Trip Open or Trip Setting

0 to 1

---

1

F727

1