Modbus Memory Map

138

4

E19F

...Repeated for module number 28

E1BF

...Repeated for module number 29

E1DF

...Repeated for module number 30

Source Group Settings (Read/Write Settings) (30 Modules)

E1FF

SRC X IOC Enabled (16 items)

0 to 1

---

1

F718

1

E20F

SRC X IOC Pickup Setting Multiplier (16 items)

1.5 - 15

---

0.5

F001

6

E21F

SRC X Short Time Protection Switch (16
items)

0 to 1

---

1

F102

1

E22F

SRC X Short Time Pickup Setting (16 items)

1.5 to 9.0

---

0.5

F001

4

E23F

SRC X Short Time I2T Curve (16 items)

0 to 2

---

1

F725

0

E24F

SRC X Short Time Delay Band Setting (16
items)

0 to 6

---

1

F713

2 (band 3)

E25F

SRC X Long Time Delay Band Setting (16
items)

0 to 3

---

1

F711

1 (band 2)

E26F

SRC X GF Protection Switch (16 items)

0 to 1

---

1

F102

0

E27F

SRC X GF Protection Trip Pickup Setting (16
items)

.2 to.6

---

0.01

F001

0.24

E28F

SRC X GF Protection Trip I2T Curve (16 items)

0 to 1

---

1

F102

1

E29F

SRC X GF Protection Trip Delay Band Setting
(16 items)

0 to 6

---

1

F713

2 (band 3)

E2AF

SRC X GF Protection Trip Priority (16 items)

0 to 30

---

1

F001

0

E2BF

SRC X GF Protection Alarm Enable (16 items)

0 to 1

---

1

F102

0

E2CF

SRC X GF Protection Alarm Pickup Setting
(16 items)

0.2 to 0.6

---

0.01

F001

0.24

E2DF

SRC X GF Protection Alarm I2T Curve (16
items)

0 to 1

---

1

F102

1

E2EF

SRC X GF Protection Alarm Delay Band Set-
ting (16 items)

0 to 6

---

1

F713

2 (band 3)

E2FF

...Repeated for module number 2

E3FF

...Repeated for module number 3

E4FF

...Repeated for module number 4

E5FF

...Repeated for module number 5

E6FF

...Repeated for module number 6

E7FF

...Repeated for module number 7

E8FF

...Repeated for module number 8