GE Industrial Solutions Entellisys 5.0 Integrator's Guide User Manual

Page 85

Advertising
background image

85

4

3832

SRC X OF Alarm Enable

0 to 1

---

1

F102

0

3833

SRC X OF Alarm Pickup Setting

50 to 70

Hz

1

F001

50

3834

SRC X OF Alarm Time Delay

0.1 to 600

---

0.1

F001

15

3835

SRC X OF Alarm Blocking Voltage Enable

0 to 1

---

1

F102

0

3836

SRC X HRGF Enable

0 to 1

---

1

F102

0

3837

SRC X HRGF Pickup

0.1 to 10

---

0.1

F001

2

3838

SRC X HRGF Delay

0.5 to 5

---

0.1

F001

0.5

3839

SRC X HRGF Ground Resistance

5 to 500

---

1

F001

5

383A

SRC X HRGF CT Rating

10 to 10

---

1

F001

10

383B

Reserved (8 items)

---

---

---

---

---

3843

SRC X High Curr Trigger Alarm Enable

0 to 1

---

1

F102

0

3844

SRC X High Curr Trigger Alarm Pickup Set-
ting

0.1 to 9

---

0.1

F001

2

3845

SRC X High Curr Trigger Alarm Delay Setting

1 to 120

---

1

F001

12

3846

SRC X High Curr Trigger Alarm WFC Enable

0 to 1

---

1

F102

0

3847

SRC X High Curr Trigger Alarm Max WF

0 to 30

---

1

F001

15

3848

SRC X High Curr Trigger Alarm WF Triggered

0 to 30

---

1

F001

0

3849

SRC X High Curr Trigger Alarm WF Count
Reset

0 to 1

---

1

F126

0

384A

SRC X Settings Reserved (40 items)

3872

...Repeated for module number 2

3926

...Repeated for module number 3

39DA

...Repeated for module number 4

3A8E

...Repeated for module number 5

3B42

...Repeated for module number 6

3BF6

...Repeated for module number 7

3CAA

...Repeated for module number 8

3D5E

...Repeated for module number 9

3E12

...Repeated for module number 10

3EC6

...Repeated for module number 11

3F7A

...Repeated for module number 12

402E

...Repeated for module number 13

40E2

...Repeated for module number 14

Advertising