System Status

31

2

2.1.9 Over (and Under) Frequency Operand States

Each breaker has 6 different states shown in

Table 2-20

. Each one of them corresponds to a

different bit in the data item.

Table 2-20 Over Frequency status bit field

The breaker states for all 30 breakers span across 12 consecutive modbus registers as shown in

Table 2-21

. See

Over Frequency Operand States (12 items) on page 136

and

Under Frequency

Operand States (12 items) on page 136

for memory locations.

Table 2-21 Over Frequency status offsets

Bit

Value

0

Alarm Pickup

1

Alarm Operated

2

Alarm Dropout

3

Trip Pickup

4

Trip Operated

5

Trip Dropout

Breaker Number

Register
Offset

Bit Offset

Notes

Breaker 1

0

0

Breaker 2

0

6

Breaker 3

0

12

Spans over two registers

Breaker 4

1

2

...

...

...

Breaker 30

11

4