Modbus Memory Map

84

4

3804

SRC X Rev Power Alarm Pickup Setting

10 to 990

kW

10

F001

990

3805

SRC X Rev Power Alarm Time Delay

0.5 to 600

S

0.5

F001

15

3806

SRC X Rev Power Trip or Open

0 to 1

---

1

F727

1

3807

Source Settings Reserved 4 (4 items)

380B

SRC X High Curr Alarm Enable

0 to 1

---

1

F102

0

380C

SRC X High Curr Alarm Pickup Setting

50 to 200

%

5

F001

200

380D

SRC X High Curr Alarm Time Delay

1 to 15

S

1

F001

15

380E

Source Settings Reserved 5 (5 items)

3813

SRC X Total Breaker Operations

0 to 65535

---

1

F001

0

3814

SRC X Total Breaker No Load Operations

0 to 65535

---

1

F001

0

3815

SRC X Total Breaker Load Operations

0 to 65535

---

1

F001

0

3816

SRC X Total Breaker Fault Operations

0 to 65535

---

1

F001

0

3817

SRC X Breaker Percent Load Life

0 to 65535

---

1

F001

0

3818

SRC X Percent Mechanical Life

0 to 65535

---

1

F001

0

3819

SRC X Time Date Last Breaker Operation

0 to 4294967295

---

F050

0

381B

SRC X Time Date Initial Energization

0 to 4294967295

---

F050

0

381D

SRC X Breaker Service Hours

0 to 4294967295

---

1

F003

0

381F

Source Settings Reserved 5 (5 items)

3824

SRC X UF Trip Enable

0 to 1

---

1

F102

0

3825

SRC X UF Trip Pickup Setting

45 to 60

Hz

1

F001

45

3826

SRC X UF Trip Time Delay

0.1 to 600

S

0.1

F001

30

3827

SRC X UF Trip Blocking Voltage Enable

0 to 1

---

1

F102

0

3828

SRC X UF Trip or Open setting

0 to 1

---

1

F727

1

3829

SRC X UF Alarm Enable

0 to 1

---

1

F102

0

382A

SRC X UF Alarm Pickup Setting

45 to 60

Hz

1

F001

45

382B

SRC X UF Alarm Time Delay

0.1 to 600

---

0.1

F001

15

382C

SRC X UF Alarm Blocking Voltage Enable

0 to 1

---

1

F102

0

382D

SRC X OF Trip Enable

0 to 1

---

1

F102

0

382E

SRC X OF Trip Pickup Setting

50 to 70

Hz

1

F001

70

382F

SRC X OF Trip Time Delay

0.1 to 600

S

0.1

F001

30

3830

SRC X OF Trip Blocking Voltage Enable

0 to 1

---

1

F102

0

3831

SRC X OF Trip or Open setting

0 to 1

---

1

F727

1