11 under voltage flex relay operand states – GE Industrial Solutions Entellisys 5.0 Integrator's Guide User Manual

Page 33

Advertising
background image

System Status

33

2

2.1.11 Under Voltage Flex Relay Operand States

There are 16 Over Voltage and 16 Under Voltage Flex Relays. Each relay has 6 different states shown
in

Table 2-24

. Each one of them corresponds to a different bit in the data item.

Table 2-24 Over Voltage status bit field

The relay states for all 16 relays span across 6 consecutive modbus registers as shown in

Table 2-25

.

See

Under Voltage Relay Flex Operand States (6 items) on page 136

for memory locations.

Table 2-25 Over Voltage Flex status offsets

Bit

Value

0

Alarm Pickup

1

Alarm Operated

2

Alarm Dropout

3

Trip Pickup

4

Trip Operated

5

Trip Dropout

Breaker Number

Register
Offset

Bit Offset

Notes

Relay 1

0

0

Relay 2

0

6

Relay 3

0

12

Spans over two registers

Relay 4

1

2

...

...

...

Relay 16

5

10