Entellisys Status Definitions

44

2

2.2.7 Synch Check Operand States

Each relay has 10 different states shown in

Table 2-44

. Each one of them corresponds to a different

bit in the data item.

Table 2-44 Synch Check status bit field

The relay states for all12 relays span across 8 consecutive modbus registers as shown in

Table 2-45

.

See

Synch Check Operand States (8 items) on page 136

for memory locations.

Table 2-45 Synch Check status offsets

Bit

Value

0

Dead Source Operated

1

Dead Source Dropout

2

Synch Operated

3

Synch Dropout

4

Close Operated

5

Close Dropout

6

V1 Above Minimum

7

V2 Above Minimum

8

V1 Below Maximum

9

V2 Below Maximum

Zone Number

Register
Offset

Bit Offset

Notes

Relay 1

0

0

Relay 2

0

10

Spans over two registers

Relay 3

1

4

Relay 4

1

14

Spans over two registers

Relay 5

2

8

Spans over two registers

Relay 6

3

2

Relay 7

3

12

Relay 8

4

6

Relay 9

5

0

Relay 10

5

10

Relay 11

6

4

Relay 12

6

14

7

8

Bits from 8 thru 15 are not used
and will always be set to 0