6 summation msgf zone operand states – GE Industrial Solutions Entellisys 5.0 Integrator's Guide User Manual
Page 43
Advertising
Multipoint FlexLogic Operand States
43
2
2.2.6 Summation MSGF Zone Operand States
Each zone has 7 different states shown in
Table 2-42
. Each one of them corresponds to a different
bit in the data item.
Table 2-42 Summation MSGF Zone status bit field
The zone states for both zones reside in a single modbus register as shown in
Table 2-43
. See
Interface (Read/Write Settings) on page 135
for memory locations.
Table 2-43 Summation MSGF Zone status offsets
Bit
Value
0
Trip Dropout
1
Alarm Dropout
2
Trip Pickup
3
Alarm Pickup
4
Trip Operated
5
Alarm Operated
6
Trip Restrained
Zone Number
Register
Offset
Bit Offset
Notes
Zone 1
0
0
Zone 2
0
8