GE Industrial Solutions Entellisys 5.0 Integrator's Guide User Manual

Page 67

Advertising
background image

67

4

0B32

...Repeated for module number 27

0B3C

...Repeated for module number 28

0B46

...Repeated for module number 29

0B50

...Repeated for module number 30

Reduced Let Thru Command

0B5A

Remote Multipoint Reduced Let Thru Enable

0 to 1

---

1

F126

0

0B5B

Remote Multipoint Reduced Let Thru Reset

0 to 1

---

1

F126

0

0B5C

Remote Multipoint Reduced Let Thru Factory
Rst All

0 to 1

---

1

F126

0

0B5D

Remote System Reduced Let Thru Enable

0 to 1

---

1

F126

0

0B5E

Remote System Reduced Let Thru Reset

0 to 1

---

1

F126

0

0B5F

Remote System Reduced Let Thru Factory
Rst All

0 to 1

---

1

F126

0

0B60

Reserved (11 Items)

0 to 1

---

1

F126

0

Reduced Let Thru Setting (Read/Write)

0B6B

FlexLogic Multipoint Reduced Let Thru Trig-
ger

0 to 65535

---

1

F300

0

0B6C

FlexLogic System Reduced Let Thru Trigger

0 to 65535

---

1

F300

0

0B6D

Reduced Let Thru Alarm Reactivation Time

1 to 24

Hour

1

F001

24

0B6E

Reserved (6 Items)

Reduced Let Thru Status (Read Only)

0B74

Reduced Let Thru Status

0 to 4294967295

---

1

F739

0

0B76

FlexLogic Multipoint Reduced Let Thru State

0 to 1

---

1

F108

0

0B77

FlexLogic System Reduced Let State

0 to 1

---

1

F108

0

0B78

Remote Reduced Let Thru Command Feed-
back

0 to 4294967295

---

1

F739

0

0B7A

Remote Multipoint Reduced Let Thru Enable
Count

0 to 8

---

1

F001

0

0B7B

Remote System Reduced Let Thru Enable
Count

0 to 8

---

1

F001

0

0B7C

Reserved (7 Items)

---

---

---

---

---

SRC X Reduced Let Thru Command (30 Modules)

0B84

SRC X Remote Reduced Let Thru Enable
Load

0 to 1

---

1

F126

0 (No)

0B85

SRC X Remote Reduced Let Thru Reset Load

0 to 1

---

1

F126

0 (No)