Modbus Memory Map

NOTE: A multiplier factor may be necessary in cases where an integer value is returned but the
Range and/or Step imply a greater precision. In these cases, it is necessary to divide the
returned value by 10 for a step of “0.1” or “0.5”; by 100 for a step of “.01”; and so on. Similarly, it is
necessary to multiply by these factors prior to writing a settings value. This note does not apply
to any step value greater than 1 (a step of “10” does not require a multiplier, for example). This
note also does not apply to values returned in floating point format. See the format codes at the
end of the map for more information.

NOTE: Discrete I/O output state registers (Contact Output x State - register range from x9180
to x91FF and Contact Output States - register range from xB256 to 0xB25D) contain correct
information only when FlexLogic Active register (x0034) contains value 1 (yes).

Addr

Register Name

Range

Units

Step

For-
mat

Factory Default

Product Information (Read Only)

0000

FBW Product Type

0 to 65535

---

1

F716

0

0001

CPU Serial Number

---

---

---

F203

"0"

0009

External Ethernet MAC Address

---

---

---

F072

0

000C

Reserved (3 items)

---

---

---

F072

0

000F

CPU Hardware Version

0 to 655.35

---

0.01

F001

1

0010

CPU Firmware Version

0 to 655.35

---

0.01

F001

1

0011

CPU Firmware Boot Code Version

0 to 655.35

---

0.01

F001

1

0012

Build Date

---

---

---

F200

"0"

0026

Synchronizer Board Status

0 to 1

---

1

F102

0

0027

Synchronizer Board Frequency Setting

50 to 60

Hz

10

F001

60

0028

Last Energy Clear Date

0 to 4294967295

---

1

F050

0

002A

Last CPU Commissioned Date

0 to 4294967295

---

1

F050

0

002C

Expected Node Protocol Version

0 to 255

---

1

F001

1

002D

Summary Number

---

---

---

F205

"0"

0033

Line Up

0 to 99

---

1

F001

1

0034

System Frequency Detected

0 to 1000

Hz

1

F001

0

Advertising