2.1.5 LT Overcurrent Operand States

Each breaker has 3 different states shown in

Table 2-12

. Each one of them corresponds to a

different bit in the data item.

Table 2-12 LT Overcurrent status bit field

The breaker states for all 30 breakers span across 6 consecutive modbus registers as shown in

Table 2-13

. See

PLC Interface (Read/Write Settings) on page 135

for memory locations.

Table 2-13 LT Overcurrent status offsets

Bit

Value

0

Alarm Pickup

1

Alarm Operated

2

Alarm Dropout

Breaker Number

Register
Offset

Bit Offset

Notes

Breaker 1

0

0

Breaker 2

0

3

Breaker 3

0

6

Breaker 4

0

9

Breaker 5

0

12

Breaker 6

0

15

Spans over two registers

Breaker 7

1

2

...

...

...

Breaker 30

5

10