Entellisys Status Definitions

32

2

2.1.10 Over (and Under) Voltage Operand States

Each breaker has 6 different states shown in

Table 2-22

. Each one of them corresponds to a

different bit in the data item.

Table 2-22 Over Voltage status bit field

The breaker states for all 30 breakers span across 12 consecutive modbus registers as shown in

Table 2-23

. See

Over Voltage Operand States (12 items) on page 136

and

Under Voltage

Operand States (12 items) on page 136

for memory locations.

Table 2-23 Over Voltage status offsets

Bit

Value

0

Alarm Pickup

1

Alarm Operated

2

Alarm Dropout

3

Trip Pickup

4

Trip Operated

5

Trip Dropout

Breaker Number

Register
Offset

Bit Offset

Notes

Breaker 1

0

0

Breaker 2

0

6

Breaker 3

0

12

Spans over two registers

Breaker 4

1

2

...

...

...

Breaker 30

11

4