GE Industrial Solutions Entellisys 5.0 Integrator's Guide User Manual

Page 83

Advertising
background image

83

4

37DB

SRC X UV Alarm Enable

0 to 1

---

1

F102

0

37DC

SRC X UV Alarm Curve Type

0 to 1

---

1

F726

1

37DD

SRC X UV Alarm Pickup Setting

10 to 95

%

1

F001

50

37DE

SRC X UV Alarm Time Delay

0.5 to 600

---

0.5

F001

15

37DF

SRC X UV Alarm Phase Requirement

1 to 3

---

1

F001

1

37E0

SRC X UV Alarm Block Volt Enable

0 to 1

---

1

F102

0

37E1

SRC X UV Alarm Block Volt Setting

5 to 75

%

1

F001

5

37E2

SRC X OV Trip Enable

0 to 1

---

1

F102

0

37E3

SRC X OV Trip Pickup Setting

105 to 125

%

1

F001

120

37E4

SRC X OV Trip Time Delay

0.5 to 600

S

0.5

F001

30

37E5

SRC X OV Trip Phase Requirement

1 to 3

---

1

F001

1

37E6

SRC X OV Trip Open or Trip Setting

0 to 1

---

1

F727

1

37E7

SRC X OV Alarm Enable

0 to 1

---

1

F102

0

37E8

SRC X OV Alarm Pickup Threshold

105 to 125

%

1

F001

120

37E9

SRC X OV Alarm Time Delay

0.5 to 600

---

0.5

F001

15

37EA

SRC X OV Alarm Phase Requirement

1 to 3

---

1

F001

1

37EB

Source Settings Reserved 2 (7 items)

37F2

SRC X PL Trip Enable

0 to 1

---

1

F102

0

37F3

SRC X PL Trip Pickup Setting

8 to 50

%

1

F001

8

37F4

SRC X PL Trip Time Delay

0.5 to 600

S

0.5

F001

30

37F5

SRC X PL Trip Block Volt Enable

0 to 1

---

1

F102

0

37F6

SRC X PL Open or Trip Setting

0 to 1

---

1

F727

1

37F7

SRC X PL Alarm Enable

0 to 1

---

1

F102

0

37F8

SRC X PL Alarm Pickup Setting

8 to 50

%

1

F001

8

37F9

SRC X PL Alarm Time Delay

0.5 to 600

S

0.5

F001

15

37FA

SRC X PL Alarm Block Volt Enable

0 to 1

---

1

F102

0

37FB

SRC X PL Trip Voltage Setting

5 to 5

%

1

F001

5

37FC

SRC X PL Alarm Blocking Voltage Setting

5 to 5

%

1

F001

5

37FD

Source Settings Reserved 3 (3 items)

3800

SRC X Rev Power Trip Enable

0 to 1

---

1

F102

0

3801

SRC X Rev Power Trip Pickup Setting

10 to 990

kW

10

F001

990

3802

SRC X Rev Power Trip Time Delay

0.5 to 600

S

0.5

F001

30

3803

SRC X Rev Power Alarm Enable

0 to 1

---

1

F102

0