Entellisys Status Definitions
38
2
2.2.2 MSGF Overcurrent Operand States
Each zone has 7 different states shown in
Table 2-34
. Each one of them corresponds to a different
bit in the data item.
Table 2-34 MSGF Overcurrent status bit field
The zone states for all 4 instances span across 2 consecutive modbus registers as shown in
Table 2-
35
. See
MSGF Overcurrent Operand States (2 items) on page 136
for memory locations.
Table 2-35 MSGF Overcurrent status offsets
Bit
Value
0
Trip Dropout
1
Alarm Dropout
2
Trip Pickup
3
Alarm Pickup
4
Trip Operated
5
Alarm Operated
6
Backup Trip Operated
Zone Number
Register
Offset
Bit Offset
Notes
Zone 1
0
0
Zone 2
0
7
Zone 3
0
14
This zone’s information spans
over two registers
Zone 4
1
5
1
12
Bits from 12 thru 15 are not used
and will always be set to 0