Entellisys Status Definitions

38

2

2.2.2 MSGF Overcurrent Operand States

Each zone has 7 different states shown in

Table 2-34

. Each one of them corresponds to a different

bit in the data item.

Table 2-34 MSGF Overcurrent status bit field

The zone states for all 4 instances span across 2 consecutive modbus registers as shown in

Table 2-

35

. See

MSGF Overcurrent Operand States (2 items) on page 136

for memory locations.

Table 2-35 MSGF Overcurrent status offsets

Bit

Value

0

Trip Dropout

1

Alarm Dropout

2

Trip Pickup

3

Alarm Pickup

4

Trip Operated

5

Alarm Operated

6

Backup Trip Operated

Zone Number

Register
Offset

Bit Offset

Notes

Zone 1

0

0

Zone 2

0

7

Zone 3

0

14

This zone’s information spans
over two registers

Zone 4

1

5

1

12

Bits from 12 thru 15 are not used
and will always be set to 0