Battery Safety Notes

Any gelled or liquid emissions from a valve-regulated lead-acid (VRLA) battery contains diluted sulfuric acid, which is

harmful to the skin and eyes. Emissions are electrolytic and are electrically conductive and corrosive.
To avoid injury:

• Always wear eye protection, rubber gloves, and a protective vest when working near batteries. To avoid

battery contact, remove all metallic objects, (such as rings or watches), from your person.

• Batteries produce explosive gases. Keep all open flames and sparks away from batteries.
• Use tools with insulated handles, do not rest any tools on top of batteries.
• If any battery emission contacts the skin, wash immediately and thoroughly with water. Follow your company’s

approved chemical exposure procedures.

• Neutralize any spilled battery emission with the special solution contained in an approved spill kit or with

a solution of one pound bicarbonate of soda to one gallon of water. Report a chemical spill using your

company’s spill reporting structure and seek medical attention if necessary.

• Prior to handling the batteries, touch a grounded metal object to dissipate any static charge that may have

developed on your body.

• Use special caution when connecting or adjusting battery cabling. An improperly or unconnected battery cable

can make contact with an unintended surface that can result in arcing, fire, or a possible explosion.

• A battery showing signs of cracking, leaking, or swelling should be replaced immediately by authorized

personnel using a battery of identical type and rating.

Battery Maintenance Guidelines

• During maintenance visits, inspect batteries for the following:

• Signs of battery cracking, leaking or swelling. The battery should be replaced immediately by

authorized personnel using a battery of the identical type and rating.

• Signs of battery cable damage. Battery cable should be replaced immediately by authorized

personnel using replacement parts specified by vendor.

• Loose battery connection hardware. Refer to documentation for the correct torque and connection

hardware for the application.

• Always replace batteries with those of an identical type and rating. Match conductance, voltage and date codes.
• Do not attempt to remove the vents (valves) from the AlphaCell broadband battery or add water. This is a safety

hazard and voids the warranty.

• Apply NO-OX grease on all exposed connections.
• When necessary, clean up any spilled electrolyte in accordance with all federal, state, and local regulations or codes.
• Follow approved storage instructions.
• Always replace batteries with those of an identical type and rating. Never install untested batteries.
• Do not charge batteries in a sealed container. Each individual battery should have at least 1/2 inch of space between

it and all surrounding surfaces to allow for convection cooling.

• All battery compartments must have adequate ventilation to prevent an accumulation of potentially dangerous gas.

Never place batteries in a sealed enclosure. Extreme caution should be used when maintaining and collecting data on

the battery system. Ensure all enclosure vents and filters are clean and free of debris.

• Spent or damaged batteries are environmentally unsafe. Always recycle used batteries. Refer to local codes for

proper disposal of batteries.