87

017-882-B0-001 Rev. C2 (10/2013)

3.0

Operation

3.0

Operation, continued

3.6 Smart Display Glossary, continued

Percent Load: The percentage of the output current versus the rated output current.
Power Supply Priority Level: The operator may select the Power Supply priority level in context of its deployed

location in the cable network. This setting is a reference for the customers only and does not affect the Power

Supply performance. The settings are Normal (default), High, or Critical.
REFRESH Enable: This enables a 24-hour REFRESH charge of the batteries. This is recommended for batteries

that have been in storage.
Reset Standby: This resets the Standby Total and Standby Events.
REST Enable: Enables the REST battery charger mode. The value is read-only when Alphacell battery models

are selected, and is programmable when the battery model is Other.
RMODE: An inverter control that limits the peak output voltage.
SAG FW Vx.xx.x: The Smart AlphaGuard firmware version that is installed. This is hidden if the SAG is not installed.
SAG Option: Indication whether the Smart AlphaGuard is installed. This is automatically sensed.
SAG ################: The Smart AlphaGuard Serial Number. This is hidden if the SAG is not installed.
Self Test: When programmed to YES, the Power Supply automatically starts a Self Test. If the Power Supply is

used in a non-standby application, the Battery Capacity variable must be programmed to “0” to disable the battery

maintenance cycle portion of a Self Test.
Set Defaults: When programmed to YES, the programmable data levels (with the exception of Last Standby

Time, Total Standby Time, Standby Events, Device Address, Total Run Time, Battery Type and Language) are

reset to the original factory settings.
Set Language: The display text language can be set to English, Spanish, French, German, or Portuguese.
Standby Events: A standby events counter. This does not include Self Test events. Resetting factory defaults

does not clear

Standby Events or Standby Total.

Standby Total: The total amount of time the Power Supply has operated in standby mode. This does not include

Self Test time and represents the sum total number of minutes of AC line failure since the last time the counter

was reset. Resetting factory defaults does not clear

Standby Events or Standby Total.

System Contact: The textual identification of the contact person for the managed Power Supply, together with

information on how to contact this person. This item can be entered via the transponder Web page or status

monitoring firmware.
System Location: The physical location of the Power Supply. This item can be entered via the transponder Web

page or status monitoring firmware.
System Name: An administratively assigned name for the managed Power Supply. This item can be entered via

the transponder Web page or status monitoring system.
Test Countdown: The number of days remaining before the next scheduled automatic Self Test initiates. This

variable is programmable and you can select the day the autotest sequence will begin. This counter has no effect

if test interval is set to 0.
Test Duration: Automatic Self Test duration timer. This sets the number of minutes of a battery maintenance cycle

test. This timer applies to automatically or manually initiated tests.
Test Inhibit: Becomes active when programmed by the operator (or when the unit runs in inverter mode for more

than 5 minutes). The Power Supply delays the start of a scheduled Self Test for seven days if the test countdown

is less than seven days (See

Section 3.7, Automatic Performance Test for complete details).

Test Interval: Automatic Self Test control timer. The number of days between battery maintenance cycle tests.

Set this value to zero to disable automatic Self Test.
TM ################: The serial number of the XM3 transformer module.
Total Run Time: The amount of time (in days) the Power Supply has functioned in any mode of operation. This

is not a resetable value.
XM3 FW Vx.xx.x: The firmware version of the XM3 micro board.