Introduction

Definitions – SAG Alarms via Class Information Base (CIB)

Miswired – PS Minor

The SAG will verify a string is correctly wired before it will add it to the list of battery

strings to balance. If it detects the wires are reversed or only one battery is connected,

the alarm will activate. This alarm may also activate if a battery is outside the valid

voltage range of 9.9V to 15.7V.

High delta mean – PS Minor

The SAG compares all measured voltages to a calculated mean voltage. This is the ideal

voltage of the battery based on the total string voltage divided by the total number of

batteries in the string. The alarm activates immediately if a battery in the string gets more

than 500mV from the calculated mean voltage.

Check battery – PS Minor

The SAG keeps track of the balancing duration of all valid strings. If a string has a

battery that will not balance to within 150mV of the calculated ideal battery mean with

three weeks of balancing, then the alarm will be set. The suspect battery will be flagged

in the status monitor information. The whole string should be checked as two suspect

batteries can cause an alarm on a good battery.

Stuck relay – PS Minor

Relays isolate the battery strings. The SAG provides a safety measure by verifying that

the relays have opened before it turns on a new string. The SAG will activate the alarm

and discontinue balancing until the alarm has cleared if the relays do not open properly.

No Harness – PS Minor

The SAG will verify that there is a harness connected before evaluating any other alarms.

Not Calibrated – PS Minor

The SAG checks the calibration data stored in memory to ensure the voltage readings

are accurate. If the data is not present, the alarm is activated.