Alpha Technologies XM3-HP Series - Technical Manual User Manual

Page 96

Advertising
background image

96

017-882-B0-001 Rev. C2 (10/2013)

4.0

Maintenance

4.0

Maintenance, continued

4.4 Battery Maintenance

Lead-acid batteries contain dangerous voltages, currents, and corrosive material.

Battery installation, maintenance, service, and replacement must only be performed

by authorized personnel.

WARNING!

4.4.1 Battery Notes

• Always refer to the battery manufacturer’s recommendation for selecting correct FLOAT,

ACCEPT and REFRESH charge voltages and REST Mode setting. Failure to do so can

damage the batteries.

• Batteries are temperature sensitive. During extremely cold conditions, a battery’s charge

acceptance is reduced and requires a higher charge voltage; during extremely hot conditions,

a battery’s charge acceptance is increased and requires a lower charge voltage. To

compensate for changes in temperature, the battery charger used in the Power Supply is

temperature compensating.

• If the batteries appear to be overcharged or undercharged, first check for defective batteries

and then verify the correct charger voltage settings.

• During preventive maintenance, check battery terminals and connecting wires. Clean battery

terminal connectors and ensure they are correctly torqued (torque specifications are listed on

the top of the battery). Spray the terminals with an approved battery terminal coating such as

NO-OX.

• If installed, disconnect the Smart AlphaGuard prior to measuring battery voltage.
• Refer to the battery manufacturer’s recommendation for correct charger voltages and the

Power Supply operation manual for corresponding charger settings.

• Number the batteries (3,2,1 left to right as shown in the Installation Procedure) inside the

enclosure for easy identification (refer to the appropriate enclosure installation guide).

• Establish and maintain a battery maintenance log.
• If batteries are being stored prior to installation, recharge per manufacturer’s specifications to

ensure optimum performance and maximum battery service life.

• The XM3-HP has a refresh “boost charge” feature specifically designed to deal with a battery

coming out of storage. See

Section 1.2.3, Charger Modes of Operation for instructions on

initiating REFRESH Mode.

Advertising