Alpha Technologies XM3-HP Series - Technical Manual User Manual

Page 23

Advertising
background image

23

017-882-B0-001 Rev. C2 (10/2013)

1.0

Introduction

Fig. 1-5, Front Panel, XM3-HP Power Supply

DOCSIS

®

Communications

Module

High Efficiency

Transformer Module

Intelligent Inverter

Module

1.3 Alpha XM3-HP CableUPS

®

Layout

The Intelligent CableUPS is comprised of the following:

Transformer module, which acts as a stand-alone line conditioner. The transformer module contains a

ferroresonant transformer, ferroresonant capacitor, line isolation relay, Power Distribution Board, EMC

Filter board and the optional AlphaDOC (PIM) board, Smart AlphaGuard (SAG) and Alpha APPS card.

Intelligent Inverter Module, which is required for standby operations and contains circuitry needed for

the three-to-five-stage temperature-compensated battery charger, DC to AC inverter, AC line detectors

and Smart Display.

Optional DOCSIS Communications Module (interfaces to Inverter Module) provides remote status

monitoring and communications.

1.3.1 Side Panel Connectors

AC Input Line Cord Connector

Optional Smart AlphaGuard Connector

Optional APPS Card

Output 1 Connector

Output 2 Connector

Fig. 1-6, Side Panel, XM3-HP Power Supply

1

2

3

4
5

1

2

3

4

5

1.0

Introduction, continued

The option cards require an Inverter Module installed in order to be functional.

NOTE: