Alpha Technologies XM3-HP Series - Technical Manual User Manual

Page 22

Advertising
background image

22

017-882-B0-001 Rev. C2 (10/2013)

1.0

Introduction

1.2

Theory of Operation, continued
1.2.4 Output Voltage Modes of Operation

The XM3-HP can be configured to Fine or Coarse Mode of operation for Output Voltage

Regulation via the Power Configuration Menu (see

Section 3.3.1, Power Information and

Configuration).

Fine Mode:

In Fine Mode the power supply will maintain the tightest output voltage regulation possible,

+1/-2.5% for 89V or +1.5/-3.5% for 63V. It will automatically adjust to and from Coarse Override

Mode temporarily if:

a) The unit switches to inverter more than 2 times in a 60-day period;

b) the unit switches tap relays more than 60 times in a 60-day period.

The power supply will automatically adjust back to Fine Mode if there are less than 2 inverter

transfers and less than 15 output tap switches in a 60-day period.

Coarse Mode:

In Coarse Mode the XM3-HP will maintain a wider output voltage regulation window, +1/-5% for

89V or +1.5/-6% for 63V. In this mode the power supply switches taps as few times as possible. It

will never automatically adjust to Fine Mode once Coarse Mode is selected.

1.0

Introduction, continued