0 installation – Alpha Technologies XM3-HP Series - Technical Manual User Manual

Page 49

Advertising
background image

49

017-882-B0-001 Rev. C2 (10/2013)

2.0

Installation

Fig. 2-24, Active Alarm Table

XM3-918-HP

90V/0.4A

**ACTIVE ALARM**

OK

PWR

PM

BATT

ALM

COMM

OK

APPS

1

2

OUTPUT LED (green)

1

2

ALARM LED (red)

Condition

Output

Alarm

Normal

On

Off

Minor

Flash

Off

Major

Flash

Flash

Output Off

Off

Flash

16. If alarms do not clear after 60 seconds, press the menu key with ALM indicated above it to see the

ACTIVE ALARM list for the selected key.

17. Press UP or DOWN to select the alarm of interest.

18. Press ENTR to select the alarm and display diagnostic information. Press ESC to return to the alarm

list.

19. Enter Battery Type (or parameters) and number of battery strings. Battery type entries can be made

on the LCD.

20. Enter the battery DATE code and the MHOs (conductance) readings. Battery date and MHOs entries

can be made on the LCD (see Figs. 2-25 and 2-26).

2.2

XM3-HP Start-Up Procedure, continued
2.2.8 Power Module Configuration and Installation Procedure, continued

2.0

Installation, continued

Fig. 2-25, Enter Battery Date Code

BATT

A1

DATE

1/10

↑↓

Adjust Value

ENTR to shift field
ENTR

ESC

BATT

A1

MHOs

1000M

↑↓

Adjust Value

ENTR to save
ENTR

ESC

Fig. 2-26, Enter Battery MHOs Reading

Battery MHOs and Date Code can only be set after DOCSIS transponder has registered with CMTS.

Please wait 3 minutes after power up to enter Battery MHOs measurements.

NOTE: