Appendix

108

017-882-B0-001 Rev. C2 (10/2013)

North American Models:

908HP

910HP

915HP

918HP

918D-HP

Fine Mode Parameters

Nominal AC Input Voltage

120VAC

120VAC

120VAC, 240VAC

120VAC, 240VAC

120VAC, 240VAC

Nominal Input Frequency

60Hz

60Hz

60Hz

60Hz

60Hz

Input Frequency Tolerance (%) ±3

±3

±3

±3

±3

Input Voltage Operating

Range Tolerance (%)

-25 / +15

-25 / +15

-25 / +15

-25 / +15

-20 / +15

Input Voltage Range (VAC)

90-138

90-138

90-138, 173-276

90-138, 173-276

96-138, 192-276

Output Voltage (VAC)

63 / 89

63 / 89

63 / 89

63 / 89

63 / 89

Output Voltage Regulation (%)

-2.5 / +1

-2.5 / +1

-2.5 / +1

-2.5 / +1

-5 / +2

Maximum Rated

Output Current

8 Amps

10 Amps

15 Amps

18 Amps

18 Amps

Maximum Output Power (VA)

720

900

1350

1620

1620

Line Mode Efficiency

Up to 94%

Standby Efficiency

Up to 91%

Output Waveform

Quasi-square wave

Short Circuit Protection

<150% of maximum current rating

Transfer Characteristics

Uninterrupted output

Battery Voltage (VDC)

36

36

36

36

36

Battery Charger

Temperature Compensation

Programmable (0 to 5mV/Cell/ºC)

Bulk Charger Current

10A

5 Stages

Refresh, Bulk, Accept, Float, Rest

Mechanical

Inverter Module

Front plug in, Hot swappable Inverter Module

Dimensions H x W x D (in/mm)

7.8 x 15 (16.7 w/handle) x 10 (10.7 w/handle) / 198.1 x 381 (424.18 w/handle) x 254 (271.8 w/handle)

Weight (lb/kg)

48.5 / 22.0

49 / 22.3

60 / 27.2

60.5 / 27.5

69.4 / 31.5

Input Power Connector

(IEC 320/C20)

NEMA 5-15P Plug

NEMA 5-15P Plug

NEMA 5-20P/

NEMA 6-15P Plug

NEMA 5-20P/

NEMA 6-15P Plug

NEMA 5-20P/

NEMA 6-15P Plug

Battery Connector

Anderson style 75A

Remote Temp Sensor

Ring lug fastens to negative terminal on center battery

Display

4 line by 20 character blue LCD with soft-key menu controls

Environment

Operating Temperature

-40 to 140°F / -40 to 60°C (derate by 3.6°F / 2ºC per 1000 feet above 3000 feet)

Humidity

0 to 95% non-condensing (relative)

Agency Compliance

Safety

CSA/UL 60950-1 (2nd), UL 1778 (4th) CSA No 107.3, C/US

EMC

FCC Part 15 Class A

Specifications