3.5 Active Alarms, continued

3.5.3 BATT Alarms

The Alpha XM3-HP CableUPS detects battery alarms and displays the type of active alarm in

the Smart Display screen and the severity of alarm (e.g., Major/Minor) by means of the Inverter

Module LEDs.

Table 3-5, BATT Alarms: Classifications, Causes and Corrections

If desired, the No Battery alarm can be disabled by changing the Number of Battery Strings or Battery

Capacity to “0” in the BATT CONFIG menu.

3.0

Operation, continued

Active Alarm

Alarm type

Alarm

Category

Probable Cause of Alarm

Corrective action

Standby

Disabled

NO BATTERIES

Major

BATT

Detected the absence of batteries (alarm

inactive when battery capacity or number of

battery strings is set to 0).

1. Check Batt Breaker

2. Check Connections

3. Check Battery Fuse

YES

LOW BATT VOLTS

Major

BATT

Battery voltages below 1.833V/cell.

1. Check AC Input

2. Restore AC Input

3. Connect Generator

4. Check Battery String

NO

HIGH BATT VOLTS

Major

BATT

Battery voltages above 4.5V over target

charger voltage.

1. Check Batteries

2. Replace Inverter

NO

BATTERY EOD

Major

BATT

Batteries dropped below the low voltage

shutdown level.

1. Low Battery Disconnect

YES

BATTERY FAIL

Major

BATT

Charge current > 5.0A for 7 days while in float

mode.

1. Check Batteries

2. Replace Batteries

NO

BATT TEMP PROBE

Minor

BATT

Precision Temperature Sensor (PTS) failed or

is not installed.

1. Check Connection

2. Replace Sensor

NO

REFRESH/BATT REFRESH

ALARM

Minor

BATT

Battery Temperature Exceeded 60°C.

1. Check Charger Settings

2. Check Batteries

3. Check Battery

Temperature

NO

SAG OPTION

Minor

BATT

I2C has failed between XM3 and SAG.

1. Check Ribbon Cable

2. Replace SAG

NO

SAG DELTA MEAN

Minor

BATT

Battery voltage is either too high or low from

mean.

1. Check Batteries

2. Replace Batteries

NO

SAG RELAY STUCK

Minor

BATT

Relay has stuck or 36V or 0V wire is no

longer connected.

1. Check SAG Wires Battery

2. Check SAG Wires Unit

3. Replace SAG

NO

STR X MISWIRED

Minor

BATT

Battery wires are not connected properly or

battery voltage is outside valid range of 9.9V

to 15.7V.

1. Check SAG Wires Battery

2. Check SAG Wires Unit

3. Replace SAG Wires

NO

SAG NOT CALIBRAT

Minor

BATT

Calibration data is not or is no longer

available.

1. Replace SAG

NO

X BAL STAGE

Minor

BATT

Stage 0 and 1 are normal. Stage 2 shows

that the batteries are not of similar capacity.

Stage 3-5 trigger check battery alarm to show

that there is a major capacity imbalance.

1. Check Batteries

2. Replace Batteries

NO

SAG NO HARNESS

Minor

BATT

Battery wires are not connected properly.

1. Check SAG Wires Battery

2. Check SAG Wires Unit

3. Replace SAG Wires

NO

NOTE:

Setting the number of strings or capacity to zero will disable the inverter, and the unit will no longer have

backup capability. At the time batteries are installed, set the number of batteries and the battery type or battery

capacity to enable battery charger and allow the XM3 to go into Self Test and Standby.