3.0

Operation

3.1 Start-Up and Test

3.1.1 Self Test Operation

1. The Power Supply should be operating correctly with no alarms present. Use the Smart Display

to verify Normal and Communication Information. Verify Test Duration setting in the Power

Config menu screen.

2. Press the Self Test button on the Inverter Module to start Self Test. The test will run for a preset

time (5-180 minutes, set in the Power Config Menu). Self Test can also be entered by setting Self

Test to ON in the Power Config Menu. Additionally, the Self Test can be configured to perform a

deep-discharge of 10%, 20%, 30%, 40% and 50% of battery capacity. When the deep discharge

is complete, it will revert back to the Timed Test.

3. While in Self Test mode, use the Smart Display or a true RMS voltmeter to verify output. Output

voltages should appear within the ranges listed in Table 3-1. To cancel a Self Test in progress,

press the Self Test button a second time or change Self Test to OFF in the Power Config Menu.

Voltage Regulation (% Range)

Voltage Setting

Fine (-2.5%/+1%)

Coarse (-5%/+1%)

89VAC

86.77VAC / 89.89VAC

84.6VAC / 89.89VAC

63VAC

61.43VAC / 63.63VAC

59.85VAC / 63.63VAC

Table 3-1, AC Output

3.0 Operation

Possible measurement points for output voltage are an unused output connector or the SPI coax

seizure screw.

NOTE: