18

017-882-B0-001 Rev. C2 (10/2013)

1.0

Introduction

1.2

Theory of Operation, continued

1.2.2 Standby Operation, continued

• When set to Individual Battery Voltage Mode, if individual battery voltage is lost, the unit automatically

reverts back to Battery String Voltage Mode and "Low Battery Cutoff” (EOD) will revert back to default

value based on battery type.

HP Batteries

GXL Batteries

OTHER Batteries

Fixed

Fixed

Fixed

String Low Battery

Cutoff (EOD)

30.6 VDC

(1.70 V/C)

31.5 VDC

(1.75 V/C)

31.5 VDC

(1.75 V/C)

Individual Low

Battery Cutoff

(EOD)

Default

Minimum

Maximum

HP Batteries

10.2 VDC

(1.70 V/C)

9.9 VDC

(1.65 V/C)

10.8 VDC

(1.80 V/C)

GXL Batteries

10.5 VDC

(1.75 V/C)

OTHER Batteries

10.5 VDC

(1.75 V/C)

• When acceptable AC line voltage returns, the Power Supply returns to AC line operation after a 10

to 20 second lag. This delay lets the AC line voltage and frequency stabilize before the control logic

phase-locks the inverter’s output to the utility input. The control logic then de-energizes the isolation

relay, reconnects the AC line to the primary of the ferroresonant transformer and disables (turns off)

the inverter. This results in a smooth, in-phase transfer back to utility power without interruption of

service to the load. The battery charging circuit then activates to recharge the batteries in preparation

for the next power outage.

1.2.3 Charger Modes of Operation

AlphaCell Batteries

OTHER Batteries

HP

GXL

Default

Minimum

Maximum

Float V/C

2.25

2.27

2.27

2.10

2.35

Accept V/C

2.35

2.40

2.40

2.20

2.45

Automatic 30-Minute

Refresh On/Off

ON

ON

OFF

OFF

OFF

Manual 24-Hour

Refresh On/Off

OFF

(Programmable)

OFF

(Programmable)

OFF

(Programmable)

OFF

ON

Refresh V/C

2.45

2.45

2.45

2.40

2.50

Rest On/Off

ON

OFF

OFF

(Programmable)

OFF

ON

Temperature

Compensation

-4mV / ºC / cell

-5mV / ºC / cell

-5mV / ºC / cell

(Programmable)

0 mV / ºC / cell

-5mV / ºC / cell

1.0

Introduction, continued

Table 1-1, Low Battery Cutoff (EOD)

Table 1-2, Charger Modes of Operation

If a battery type other than an AlphaCell is installed, it is the responsibility of the technician to review the proper

charging specifications for the battery used.

NOTE: