0 operation, Pwr cnfg <entr> output volts output curr entr esc, 0 operation, continued – Alpha Technologies XM3-HP Series - Technical Manual User Manual

Page 63

Advertising
background image

63

017-882-B0-001 Rev. C2 (10/2013)

3.0

Operation

3.3

Smart Display Menus, continued

3.3.1 Power Information and Configuration

Pressing the PWR (Power) softkey while in the OPERATION NORMAL screen opens the Power Info

Menu display (the first letter of the top line will blink indicating it is the active line; shown in orange).

Pressing ENTR from this screen opens the PWR CNFG Menu. Cycling through each menu item

and following the prompts on the lower line will enable the user to configure the parameters shown

in the menu.

P

WR CNFG <ENTR>

OUTPUT VOLTS
OUTPUT CURR
ENTR

ESC

Power Info Menu

Default

Range

PWR CNFG <ENTR>
OUTPUT VOLTS

63 or 89 VAC

0–101 VAC

OUTPUT CURRENT

10.5A

0–40 A

OUTPUT 1 CURRENT

6.8A

OUTPUT 2 CURRENT

8.0A

N+1 VALID*

YES/NO

OUTPUT POWER

2000W

PERCENT LOAD

80%

0–255%

INPUT VOLTS

120V

0–325 VAC

INPUT CURRENT

(4.5A)

0–25 A

INPUT FREQ

60HZ

42HZ–67.5HZ

INPUT POWER

2000W

OPER MODE

LINE/STANDBY

STANDBY EVENTS

0–65535 EVENTS

CURRENT OUTAGE

0–65535 MIN

LAST OUTAGE

0–65535 MIN

LAST EVENT

(DD:HH:MM)

TOTAL RUN TIME

0–65535 DAYS

STANDBY TOTAL

0–65535 MIN

LAST STBY RESET

0–65535 DAYS

XM3 FIRMWARE

V

x

,

xx

,

x

TM #######
IM ########
BATT INFO

<ENTR>

Power Config Menu

Default

Range

SELF TEST

OFF

ON / OFF

TEST INTERVAL

30 DAYS

0 –365 DAYS

TEST DURATION

10 MIN

5–180 MINUTES

TEST COUNTDOWN

30 DAYS

0–365 DAYS

TEST INHIBIT

+7 Days=Test Inhibit

0=OFF

DISCHARGE LVL

TIMED

TIMED, 10–50%

FREQ RANGE

3.0HZ

1–6HZ

ALPHADOC OPTION

AUTO

NO / YES

ALPHADOC FW

VX.XX.X

DOC #####
OUTPUT 1 RESET

ON

NO

1

OUTPUT 2 RESET

ON

NO

1

CURR LIMIT 1

110% RATING 3.0–25.0A

2

CURR LIMIT 2

110% RATING 3.0–25.0A

2

RETRY DELAY

60S

5–301S

2

RETRY LIMIT

20

0–40

2

OVER CURR TOL

3000MS

20–9900MS

2

OUTPUT VOLT REG

3

FINE/COARSE

RMODE

DISABLE

ENABLE/DISABLE

PS PRIORITY

NORMAL

INPUT LIMIT
INP V SETTING

4

120V/240V

SET DEFAULTS

NO

NO / YES

RESET STANDBY

NO

NO / YES

DEVICE ADDRESS

1

0–5

SELECT LANGUAGE

English

Spanish, French,

Portuguese, German

Hidden if no

AlphaDOC is

installed

3.0

Operation, continued

* Displayed only if AlphaDOC with N+1 option is installed

1

Output 1 & 2 Reset will be hidden if the corresponding output is not tripped.

2

Ablity to select available if Optional AlphaDOC installed

3

Hidden for XM3-918D-HP models

4

Displayed only for XM3-918D-HP models