Alpha Technologies XM3-HP Series - Technical Manual User Manual

Page 32

Advertising
background image

32

017-882-B0-001 Rev. C2 (10/2013)

1.0

Introduction

LED ALARM STATES

LED

name

Color

State

Function

Active

Green

Off

No power to SAG

Solid

Unit is on and communicating

with Power Supply or in Rest

mode

Flash (90% on / 10% off)

Unit is on and not communicating

with Power Supply

Flash (50% on / 50% off)

Actively balancing

Flash (10% on / 90% off)

Powersave mode

STRG A

STRG B

STRG C

STRG D

(ALARMS)

Red

Off

Normal operation

No string wires connected

Flash (50% on / 50% off)

High delta mean

Check battery alarm

Flash (10% on / 90% off)

Stuck relay alarm

Solid

String A missing

String miswired

Battery outside valid range

ALL STRG

No harness connected or all

strings are miswired

1.3.4.4 LEDs

The LEDs provide visual indications of the current state of the SAG and any alarms that

are present.

1.3

Alpha XM3-HP CableUPS Layout, continued
1.3.4 Smart AlphaGuard, continued

1.0

Introduction, continued

Fig. 1-13, SAG Front Panel

Table 1-4, Smart AlphaGuard LED Alarm States

SAG front panel