0 operation – Alpha Technologies XM3-HP Series - Technical Manual User Manual

Page 76

Advertising
background image

76

017-882-B0-001 Rev. C2 (10/2013)

3.0

Operation

3.4.2 Applications, continued

Utility Performance App:
This application monitors the AC line input to the XM3 Power Supply. It detects, displays and

logs four types of AC fault conditions:

1. Outage – If the AC input is below a factory set threshold, an outage condition is recorded.
2. Sag – If the AC input exists but is below a factory set threshold, a line sag condition is

recorded.

3. Surge – If the AC input exceeds a factory set threshold, a line overvoltage or surge

condition is recorded.

4. Frequency – If the AC line frequency exceeds the normally defined operating range, a

frequency event is recorded.

Each condition is measured with one second resolution and will not be permanently logged until

the event has ended.
To enter the Utility Performance sub-menu, scroll up or down until UTILITY PERFORMANCE is at

the top of the scroll area.

3.4

AlphaAPPs Overview, continued

AlphaAPP

V1.05.0

U

TILITY PERFORMANCE

EVENT HISTORY

ENTR

ESC

APPS TECH ID SCREEN

ENTER TECH ID: 0
BATTERY HISTORY
UTILITY PERFORMANCE
EVENT HISTORY
CONFIG HISTORY
APPS CONFIG
BATTERY HEALTH
BATTERY EST RUNTIME

Press ENTR to access the

UTILITY PERFORMANCE

sub-menu

O

UTAGE IN PROGRESS

START TIME

23:52

DURATION

12M 13S

ENTR

ESC

OUTAGE 24 HR HISTORY

EVENTS 2, AVG 2M

MIN 1M , MAX 3M

OUTAGE TOTAL HISTORY

EVENTS 5 = 35 M

MIN 1M, MAX 10M

OUTAGE LOG

DATE/TIME/DURATION

03/19/11 22:35

99M

ESC

UTILITY PERFORMANCE
OUTAGES

OUTAGE 24 HOUR HISTORY

EVENTS 0, AVG 0

MIN 0, MAX 0

SAGS

SAG 24 HOUR HISTORY

EVENTS 0, AVG 0

MIN 0, MAX 0

SURGES

SURGE 24 HOUR HISTORY

EVENTS 0, AVG 0

MIN 0, MAX 0

FREQ

FREQ 24 HOUR HISTORY

EVENTS 0, AVG 0

MIN 0, MAX 0

3.0

Operation, continued

Advertising