0 maintenance – Alpha Technologies XM3-HP Series - Technical Manual User Manual

Page 104

Advertising
background image

104

017-882-B0-001 Rev. C2 (10/2013)

4.0

Maintenance

4.4

Battery Maintenance, continued

4.4.7 Battery Refurbishment Plan

4.0

Maintenance, continued

Does battery meet

the minimum

conductance values

per Table 4-2?

Yes

Measure

Conductance

Measure

Battery

Voltage

Sort Batteries per

Conductance &

Voltage

Batteries Returned

from Site. Measure

and document 24

hour Open Circuit

Voltage (OCV).

(

Must occur within 24

hours of removal from

charger)

Properly recycle

batteries per EPA

requirements

Battery

Refurbishment

Plan

Group re-deployable

batteries as indicated for

future deployment as

strings

No

Yes

Does battery meet

the minimum of

12.6 Volts for the 24

hour OCV?

Measure

Battery

Voltage

Batteries stored in

warehouses for

extended periods of

time refer to

Section

4.4.3, Disposal,

Recycling and Storage

Instructions

No

Fig. 4-7, Flow Chart for Battery Refurbishment Plan

1.

DO NOT mix batteries of different models within in a string. Example: 165GXL with 195GXL.

2.

DO NOT mix batteries from different manufacturers. Example: Alpha and MK.

3.

No battery age limit if it passes the other tests.