017-882-B0-001 Rev. C2 (10/2013)

1.0

Introduction

1.3

Alpha XM3-HP CableUPS Layout, continued
1.3.4 Smart AlphaGuard, continued

1.0

Introduction, continued

1.3.4.2 Connections

The connection from the embedded SAG to the battery strings are made with one of the

orderable wire kits. Kits for one, two, three, or four stings are available. Kits are also

available that mate to the external AlphaGuard wire kit. The SAG wire kit consists of a

string 36V positive and a string negative that are common for all strings. For each string

(A, B, C and D), there are two additional wires that must be connected.

Wire kits

New install with embedded SAG

1 string Battery harness p/n 875-848-20

2 string Battery harness p/n 875-848-21

3 string Battery harness p/n 875-848-22

4 string Battery harness p/n 875-848-23

Upgrade with external AlphaGuard wire kits in place

1 string Battery harness p/n 875-910-20

2 string Battery harness p/n 875-910-21

3 string Battery harness p/n 875-910-22

4 string Battery harness p/n 875-910-23

Adaptor Cable

SAG to Status Monitor p/n 876-003-20

(please contact Alpha Technologies Inc. for full details).

Single battery string

A single string system must use String A on the wire harness.

Vbatt 3A

36V

Red, Pin 9

3A

2A

1A

A/B/C/D NEG Black, Pin 5

Vbatt 2A

24V

Orange, Pin 4

Vbatt 1A

12V

Brown, Pin 10

Black

Red

Fig. 1-11, Single Battery String Wiring Diagram (w/ embedded SAG Harness depicted)

(String -) 0V

POS(+)

NEG(-)

NEG(-)

NEG(-)

POS(+)

POS(+)

1

2

3

4

6

7

8

Back of Plug

5

9

10