Alpha Technologies XM3-HP Series - Technical Manual User Manual

Page 102

Advertising
background image

102

017-882-B0-001 Rev. C2 (10/2013)

4.0

Maintenance

4.4

Battery Maintenance, continued

4.4.6 Periodic Maintenance Tasks, continued

4.0

Maintenance, continued

4.4.6.2 On-Site Battery Preventive Maintenance, continued

Procedure
1. Verify the Power Supply is in FLOAT mode.
2. Use the DC Amp clamp to measure and record each individual battery string’s float

current.

3. If the individual string float current is greater than 0.5 amps, replace the battery

string. Measure and record the individual battery conductance and voltage on the

Site Visit Record.

4. If the string float current is less than 0.5 amps,

a. Disconnect the batteries from the system.
b. Measure the battery conductance. If any reading is below the suspect level, refer

to Table 4-1, for mhos values for battery models.

c. Measure the battery voltage. If any reading is less than 12.6V then replace all

those batteries in the string.

d. If any individual battery voltage varies more than 0.5V above or below the

average for the string, replace the string.
i. Example: V1 = 13V, V2 = 13V, V3=14V
ii. Average voltage = 13.3V
iii. If V3 is greater than average by 0.5V, then the batteries should be replaced.

Batteries removed from the site should then be tested per

Section 4.4.7,

Battery Refurbishment Plan.

e. Log the site location, battery location, model, manufacturer date codes, voltage

and conductance readings for all batteries.

5. Record data on Battery Maintenance log.
6. Verify the spacing between the batteries from front to back is at least 1/2" or 13mm,

and adjacent batteries do not touch one another.

7. Ensure the enclosure is clean and free of debris.
8. Measure and record the top center battery's temperature. This is typically the

warmest battery in the string.

9. Visually inspect the batteries for:

a. Cleanliness
b. Terminal damage or evidence of heating or overheating
c. Container or cover damage

10. Check terminal posts for signs of corrosion. If corrosion is present, neutralize with a

solution of 1 lb (454g) sodium bicarbonate (baking soda) to 1 gallon (3.8l) of water.

Rinse and dry.

11. Verify terminal posts are coated with NO-OX grease or a spray-on protectant.

Reapply as needed.

12. Retorque all the interunit connecting hardware to the values noted in the tables on

the next page.

Advertising