background image

105

017-882-B0-001 Rev. C2 (10/2013)

4.0

Maintenance

4.4

Battery Maintenance, continued

4.4.8 Battery Evaluation Procedures for AlphaCell Batteries

4.0

Maintenance, continued

To help identify batteries approaching end of life in an operating power system, the following test

should be performed at each maintenance interval. For accuracy, tests must be performed on

fully charged batteries.

Conductance/Impedance Test – Measure the conductance of each battery. Any battery that

possesses a conductance that is 50% less than the initial reading taken at the point of install can

be considered suspect of being below 70% capacity and should be evaluated further. The battery

temperature must be approximately the same each time this reading is taken (see Table 4-2

below). Use temperature compensation feature when using Midtronics meter.

Float Voltage Test – Measure the float voltage of each battery in the string that is on float charge.

Any battery in the string measured at 13.2 volts or less is a suspect battery and should be further

evaluated with the steps below. Any battery below 12.6 volts should be replaced. The 13.2 & 12.6

voltage values are based on a 77˚F (25˚C) temperature. Adjust the voltage for higher or lower

temperatures by 0.0168 volts per battery per degree Fahrenheit. The higher the temperature

above 77˚ F (25˚C) the lower the voltage will have to be adjusted and vice-versa for temperature

below 77˚F (25˚C). (i.e.: at a temp of 89˚F (32˚C) would have a corresponding float voltage of

13.0 volts).

Battery Replacement Criteria –Batteries with a Siemens number of 400 or less should be

replaced. Batteries with a Siemens number between 400 and 700 and failing the 10 minute Self

Test should be replaced. If the Self Test passes, the batteries will not be replaced. Batteries with a

Siemens number greater than 700 and passing the 10 minute Self Test should not be replaced. A

battery that drops below 10.8 volts during the 10 minute Self Test is suspect.

Table 4-2, AlphaCell Conductance Values, Healthy vs. Suspect Batteries

Midtronics Conductance

Models 3200/micro CELLTRON

3.5 HP

4.0 HP

Approximate Conductance Values (MHOs)

Healthy Battery @ 77°F (25°C)

1400-1850 1700-2500

Suspect Battery @ 77°F (25°C) in MHOs

<680

<840

Midtronics Conductance

Models 3200/micro CELLTRON

85

GXL-HP

135 GXL*

160 AGM*

165 GXL

170XLT

Approximate Conductance Values (MHOs)

Healthy Battery @ 77°F (25°C)

480-720

900-1350

1040-1560

800-1200

1040-1560

Suspect Battery @ 77°F (25°C) in MHOs

<240

<450

<520

<400

<520

Midtronics Conductance

Models 3200/micro CELLTRON

195

GOLD-HP

195 GXL

195

GXL-FT*

220 GXL

220

GOLD-HP

Approximate Conductance Values (MHOs)

Healthy Battery @ 77°F (25°C)

880-1320

880-1320

800-1200

960-1400

960-1400

Suspect Battery @ 77°F (25°C) in MHOs

<440

<440

<400

<480

<480

(*) – Indicates Batteries not listed in the

menu list.