0 operation – Alpha Technologies XM3-HP Series - Technical Manual User Manual

Page 64

Advertising
background image

64

017-882-B0-001 Rev. C2 (10/2013)

3.0

Operation

3.3.2 Battery Information and Configuration

The top line of the display is affected by pressing a softkey. In this case, pressing Enter <ENTR>

will open the BATTERY INFO/BATTERYCONFIG Menu enabling the operator to set values for the

following parameters.

BATTERY INFO MENU

NOTE

BATT CONFIG <ENTR> Pressing enter goes to the Battery Configuration menu shown below
BATT VOLTS

Displays combined string voltage

CHARGER CURR

Displays Batt Current for Inverter Mode

CHARGER MODE

Displays current Charger Mode: OFF/FLOAT/REFRESH

IND BATT V

Not displayed if no DSM3 or SAG installed

BATT TEMP

Displays battery temperatures (°C)

APPS INFO <ENTR>

Pressing enter goes to the APPS/INFO menu on APPS Tab*

SAG INFO <ENTR>

Pressing enter goes to the SAG INFO menu shown at right

BATTERY CONFIG MENU

Default

Range

Note

BATT MHOS

0

0-2550

Hidden if no APPS card is installed

BATT DATES

User programmable

BATT MODEL

OTHER

AlphaCell models listed at right

BATT STR DETECT

AUTO

AUTO / MANUAL

NUM BATT STRINGS

1

1-4

BATT CAPACITY

100AH

0*, 1–1000

Automatically set when AlphaCell model is selected.

FLOAT

2.27V/C 2.10-2.35

ACCEPT

2.40V/C 2.20-2.45

REFRESH

2.45V/C 2.40-2.50

REST ENABLE

OFF

ON/OFF

TEMP COMP

5.0MV

0-5.0MV per cell

EOD TYPE

STRING IND or STRING

Individual Battery EOD only if sense harness is connected

Will display STR OVER for STRING override mode

EOD VOLT

1.75V/C

Hidden if EOD TYPE = STRING

REFESH ENABLE

ON

ON/OFF

Pressing Enter goes to adjust screen

SAG OPTION

AUTO

Auto-recognize Smart AlphaGuard (SAG)

SAG FW V1.00.0

Hidden if no SAG connected

SAG #####

Hidden if no SAG connected

HEATER MAT

NO

YES/NO

Pressing Enter goes to adjust screen

AlphaCell Batteries

4.0HP
3.5HP
220GOLD
220HPL
220GXL
210GXL
195GXL
195GOLD
180GXL
165GXL
115HPL
85GXL
70HPL
OTHER
170XLT

XM3-918-HP

90V/0.4A

OPERATION NORMAL

OK

PWR

OK

BATT

OK

COMM

OK

APPS

Individual Battery

Volts Menu

BATT A1 VOLTS*
BATT A2 VOLTS*
BATT A3 VOLTS*
BATT B1 VOLTS*
BATT B2 VOLTS*
BATT B3 VOLTS*
BATT C1 VOLTS*
BATT C2 VOLTS*
BATT C3 VOLTS*
BATT D1 VOLTS*
BATT D2 VOLTS*
BATT D3 VOLTS*
NO BATTERIES**

3.3

Smart Display Menus, continued

3.0

Operation, continued

SAG INFO

BALANCING STR*
DUR REMAIN ###### M**
A MAX DELTA #### mV**
B MAX DELTA #### mV**
C MAX DELTA #### mV**
D MAX DELTA #### mV**
A BAL STAGE MODERATE**
B BAL STAGE MODERATE**
C BAL STAGE MODERATE**
D BAL STAGE MODERATE**
A SEVERE DUR ##### M**
B SEVERE DUR ##### M**
C SEVERE DUR ##### M**
D SEVERE DUR ##### M**
BALANCER DIS YES/NO
POWERSAVE MODE YES/NO
NUM OF STRINGS ##
SAG HARDWARE ID

* Displays NONE if no strings

are being balanced

** Displays only if string is

present

* Displays only if

battery is present

** Displays if no

batteries are

present

* Displays only if Apps Card is installed

* BATT CAPACITY should only be set to "0" when no batteries are present to disable NO BATT Alarm.