017-882-B0-001 Rev. C2 (10/2013)

4.0

Maintenance

4.3.2.2 On-Site Power Supply Preventive Maintenance, continued

4.3

Power Supply System Maintenance, continued
4.3.2 Periodic Maintenance Tasks, continued

4.0

Maintenance, continued

4. Inspect Inverter Module

Whenever the battery breaker is turned off or the batteries are not connected, the CableUPS

automatically reports a No Battery alarm. This is a built in safety feature. The unit does not attempt

inverter operations, either standby or test, during a No Battery alarm.

NOTE:

ALWAYS switch the battery breaker off before removing or installing the Inverter Module

assembly.

CAUTION!

You can remove the Inverter Module assembly while the Power Supply is running on line power. The

Power Supply will continue to operate as a non-standby regulated Power Supply

NOTE:

a. Carefully remove the Inverter Module assembly.

1. Shut off battery circuit breaker and disconnect the 36V battery cable

from the Inverter Module.

2. Disconnect the LRI and Temp Probe cables from the Inverter Module

and the TMPR and XPDR cables from the communication module.

3. Loosen the thumbscrews.
4. Grasp tab at base of Communications Module sheet metal and pull

Inverter Module from the Power Supply.

b. Verify Output voltage remains with volt meter.
c. Inspect the Inverter Module for signs of dust or corrosion.
d. Reinstall the Inverter Module (reverse removal procedure) and test the

Power Supply for proper operation.
1. Turn off the utility input breaker to remove input power. The Power

Supply goes into standby operation.

2. Verify on the Smart Display that there is no interruption to the output.
3. After five minutes reapply utility power. The Power Supply then transfers

back to Operation Normal, clears any alarms and starts the battery

charger (BULK, if needed.) This test adds standby events and time to

the event counter.

5. Record the following data from the XM3 Smart Display and record in the XM3

system maintenance log:

Operational Data:
Output 1 Voltage

Output 2 Voltage (if AlphaDOC installed)

Output 1 Current

Output 2 Current (if AlphaDOC installed)

Input Voltage

Standby Events

Total Standby Time

Input Watts

Output Watts

PTS Reading

Outside Ambient