Vcb calibration – Biamp A4 User Manual

Page 159

Advertising
background image

Component Objects

External controls must be identified (see

Device Maintenance

) and associated with their

corresponding component blocks within the layout (see

Equipment Table

). The VCB will assume

a full range of 0~5 Volts returning from connected potentiometers, unless the

VCB Calibration

procedure is followed (see

Device Maintenance

). Please refer to the 'Installation Guide'

(included with controls), or see

Remote Control Bus

for more information.

VCB Calibration

Once a VCB (

Voltage Control Box

) block has been assigned in an Audia configuration, and the

VCB device (with potentiometers attached) is connected to the Audia

Remote Control Bus

, the

potentiometers can be calibrated for accurate tracking of levels (see

Device Maintenance

).

The first screen encountered in this process allows for
the selection of the potentiometer Channel to be
calibrated. Channel numbers correspond to the Analog
potentiometer connections on the VCB itself. Only one
potentiometer Channel can be calibrated at a time, and
only Channels with potentiometers actually connected
will be available.

Once the Channel
has been selected,
this screen will
prompt the user to
adjust the
corresponding
potentiometer (on
the selected
Channel) to its
maximum (highest)
physical setting,
then select "Next".

Once the maximum
potentiometer
setting has been
recorded, this
screen will prompt
the user to adjust
the same
potentiometer to its
minimum (lowest)
physical setting,
then select "Next".

139