Setting the device address, Profibus pa), Cyclic parameters – Burkert Type 8635 User Manual

Page 115

Advertising
background image

8635 - 113

C

ONFIGURATION FOR

B

US

C

OMMUNICATION

(PROFIBUS PA)

Setting the device address

Configuration and parametrization of the SIDE Control

(PROFIBUS PA) are done locally via menu

functions or via the bus. The valve can also be opened and closed locally by hand. The setpoint can

be specified via the bus.

With

DIP switch 8, one sets whether the device address is to be set on the device or via the bus

With DIP switch 8 in the OFF position, the device address can be set via

DIP switches 1 to 7. The

permissible range for the address is 3 to 124.

Cyclic parameters

SP

Setpoint of valve position

These parameters are of type DS-33 (value and status - floating point structure).The structure of this type

of parameter is shown in the following table:

The „good“ status is 0 x 80. The configuration

SP is supported.

NOTE

The DIP switch settings are read in only on switching on the device.

DIP switch 8

Setting

OFF

Enter the device address with the DIP switch

ON

Enter the device address via the bus

DIP-1

DIP-2

DIP-3

DIP-4

DIP-5

DIP-6

DIP-7

Address

2

0

2

1

2

2

2

3

2

4

2

5

2

6

ON

ON

OFF

OFF

OFF

OFF

OFF

3

"Permissi-

ble range

for

address"

:

OFF

OFF

ON

ON

ON

ON

ON

124

ON

OFF

ON

ON

ON

ON

ON

125

125

OFF

ON

ON

ON

ON

ON

ON

126

126

Element no.

Name of element

Type

Length

1

Value

Float - (8)

4 byte

2

Status

Unsigned 8 - (5)

1 byte