Burkert Type 8635 User Manual

Page 57

Advertising
background image

8635 - 55

O

PERATING AND

C

ONTROLLER

F

UNCTIONS

ADDFUNCT

see section

Configuring the supplementary functions.

➔ Jump over this menu item on first commissioning.

X.TUNE

- AUTOTUNE for positioners

Start the automatic adaptation of the positioner to the current operating
conditions (X.TUNE)

The following functions are initiated automatically:

• Adaptation of the sensor signal to the (physical) stroke of the valve used.

• Determination of parameters for driving the integral piezoelectric positioning system

• Setting of the controller parameters of the positioner.

Optimization is done according to the criteria: as short a correcting time as possible and freedom
from overshoot.

END

EEPROM

ADDFUNCT

X.TUNE

X.TUNE END

5 s

5 s

Operating mode

or

AUTOMATIC
MANUAL

Main menu for settings on commissioning

Description of procedure