8635 - 75

O

PERATING AND

C

ONTROLLER

F

UNCTIONS

SIG-ERR

Configuration of error recognition signal level (S/HART)

NOTE

Error recognition
Error recognition can be selected only with 4 ... 20 mA signal of the process value.
Error is recognized with an input signal

≤ 3.5 mA (±0.5 % of end value, hysteresis 0.5 %

of end value).
With signal error recognition activated: PV FAULT signal error of process controller value.
With the process controller deactivated,

NOT.AVAIL appears in the selection menu.

Safety position SPOS ON

If

SPOS ON is set, the following configurations may occur:

Activated menu item

SAFEPOS

On error recognition the actuator moves to the position set under

SAFEPOS.

Deactivated menu item

SAFEPOS

On error recognition the actuator moves to the end position which it would assume in the zero-voltage
state.

Activate signal error

recognition

Activate move to safety

position

SIG-ERR

ERR END

Configure error
recognition of
process value
signal

ERR P.INP

P.INP ON

SPOS ON

P.INP OFF

SPOS OFF

Move to safety
position if signal
in error