Technical data of the side control (s/hart), S/hart), Technical data (s/hart) – Burkert Type 8635 User Manual

Page 26

Advertising
background image

24 - 8635

S

YSTEM

D

ESCRIPTION

(S/HART)

OPERATING CONDITIONS

Permissible ambient temperature

-25 ... +65 °C (with non-Ex devices or T4/T5)

-25 ... +60 °C (with T6)

System of protection

IP 65 to EN 60529

(only with correctly connected cable)

CONFORMITY TO THE FOLLOWING STANDARDS

CE Symbol

Conformity wrt. EMC Guideline 89/336/EEC

Low Voltage Guidline

73/23/EEC

Explosion protection (optional)

EEX ia IIC T4/T5/T6

MECHANICAL DATA

Housing dimensions, outside (WxHxD)

174 x 88 x 93 mm

Housing material

Aluminium

hard anodized and plastic-coated

Seal material

NBR / Neoprene

Other exterior parts

stainless steel (V4A)

Mass

approx. 1.5 kg

ELECTRICAL DATA

Connections

2 M20x1.5 bushings

with screw terminals 0.14 ... 1.5 mm

2

Power supply

via setpoint input 4-20 mA

Burden voltage

< 12 V DC

Burden resistance

590

Ω at 20 mA and 11.8 V DC

Process value input (option)

4-20 mA

Burden voltage

200 mV at 20 mA

Burden resistance

10

Binary input

mechanical make/break contact

Inductive proximity switch (optional)

to DIN EN 60947-5-6 (NAMUR)

Structural shape

SJ3.5-G-N

Manufacturer

Pepperl+Fuchs

Output signal for

switching amplifier

to DIN EN 50227 (NAMUR)

Rated voltage U

0

8 V

Current (sensor uncoated)

2.1 mA

Current (sensor coated)

1.2 mA

Technical data of the SIDE Control (S/HART)

Technical data (S/HART)

Advertising