S/hart) – Burkert Type 8635 User Manual
Page 99
8635 - 97
O
PERATING THE
P
ROCESS
C
ONTROLLER
(S/HART)
Process value from transmitter:
4 ... 20 mA corresponds to 0 ... 10 l/min
Process setpoint of SPS:
4 ... 20 mA corresponds to 0 ... 8 l/min
Example of scaling for the 4 ... 20 mA input
Process
value
Scaling value
[l/min]
Process
setpoint
Input signal
[mA]
Variant 1
Variant 2
Variant 3
PV
0
0
0
PV
1.0
10.0
100.0
SP
0
0
0
SP
0.8
8.0
80.0
Example for entering scaling values
NOTE
On entering small scaling values, decimal places are automatically added to increase the
precision of display, such that the maximum possible digit range is given between the lower
and upper scaling values in each case. The amplification factor
KP of the process controller
refers to the scaling values set.
With
P.CO SETP / SETP INT (setpoint entry via the arrow keys), scaling of the setpoint via
SP und SP is not possible. The setpoint may be entered directly corresponding to the
scaled process variable
(PV , PV ).