8635 - 145

G

ENERAL

R

ULES

(A

PPENDIX

)

1
Ti

I component

Function: Y =

∫ Xd dt

Ti is the integration or floating time. It is the time that expires until the controller output has run through
the entire correcting range.

Characteristic and step resonse of the I component of a PID controller

Characteristic

Step response

Control range

∆Xc

Characteristics:

A purely I controller completely eliminates the effects of disturbances. It thus has a favourable static
behaviour. Because of its finite correcting speed, it works more slowly than a P controller and tends to
oscillation. It is hence dynamically relatively unfavourable.