I component, Characteristics – Burkert Type 8635 User Manual
Page 147
Advertising
8635 - 145
G
ENERAL
R
ULES
(A
PPENDIX
)
1
Ti
I component
Function: Y =
∫ Xd dt
Ti is the integration or floating time. It is the time that expires until the controller output has run through
the entire correcting range.
Characteristic and step resonse of the I component of a PID controller
Characteristic
Step response
Control range
∆Xc
Characteristics:
A purely I controller completely eliminates the effects of disturbances. It thus has a favourable static
behaviour. Because of its finite correcting speed, it works more slowly than a P controller and tends to
oscillation. It is hence dynamically relatively unfavourable.
Floating time
Control r