S/hart) other malfunctions – Burkert Type 8635 User Manual

Page 141

Advertising
background image

8635 - 139

M

AINTENANCE AND

E

RROR

E

LIMIN

.

ON THE

P

ROCESS

C

ONTROLLER

(S/HART)

Other malfunctions

Problem

Possible causes

Remedy

POS = 0 (with CMD > 0 %) or

Tight-closing function

Deactivate tight-closing

POS = 100 %, (with CMD < 100%) (CUTOFF) has been

function

PV = 0 (with SP > 0 ) or

inadvertently activated

PV = PV (with SP > SP )

Only with device with process
controller:

Device does not work as a

Menu item

P.CONTRL stands in

Remove the menu item

positioner despite correctly

main menu. The device thus

P.CONTRL from the main

executed settings.

works as a process controller

menu.

and expects a process value at
the corresponding input.

Error messages on execution of the function P.Q'LIN

Display

Causes of error

Remedy

Q.ERR 1

No compressed air connected

Connect compressed air

No change of process variable

Check process; if necessary, switch on
pump or open shut-off valve

Q.ERR 2

Current fixed point of the valve stroke
was not reached since

air supply failure during P.Q’LIN

Check compressed air supply

no AUTOTUNE has been executed

Execute AUTOTUNE