Hart, Hart) – Burkert Type 8635 User Manual

Page 131

Advertising
background image

8635 - 129

O

PERATING VIA THE

HART

HAND TERMINAL

(HART)

NOTE

Contrary to the execution of

PTUNE via the SIDE Control, the process value PV, and

hence the starting value for the optimization step, cannot be changed by switching over

to the MANUAL mode and opening and closing the valve.

After confirmation with

F4 - OK, the process value PV is read in for 10 s. You thus have the possibility

of checking whether the actual value is constant and you can decide whether the

PTUNE function

should be initiated (enter

Yes) or whether the process value PV should be read in again for a further

10 s (enter

No).

User query

After entry of

Yes, you now have the possibility of initiating control parameter optimization by

specifying a setpoint step.

Start PTUNE by choosing a new setpoint SP

Confirm the message with

F4 - OK.

On the HART hand terminal, the entry mask for the setpoint appears.

Entry mask for specifying a setpoint step.

Enter the new value and confirm with

F4 - ENTER.

Self-optimization of the process controller runs autonomously. On the HART hand terminal, the
following message appears:

Running PTUNE

Running of the function

PTUNE is ended by an OK message.

OK message after completion of

the function

PTUNE.