Burkert Type 8635 User Manual

Page 59

Advertising
background image

8635 - 57

O

PERATING AND

C

ONTROLLER

F

UNCTIONS

POS MIN

POS MAX

TUNE-END

TUNE-POS

A.LIM NO

A.LIM YES

EEPROM

POS-MAX

POS-MIN

EEPROM

TUNE-PWM

YB

XXX

YE

XXX

TUNE-AIR

T.OPN XX

T.CLS XX

X.TUNE

TUNE END

X.T XXX

TUNE 0

TUNE 1

TUNE 2

TUNE 3

TUNE 4

TUNE 5

AUTOTUNE

MANUAL TUNE

release

move to max.

position

move to min.

position

change min.PWM-T.V. for

pressurizing valve

change min. PWM-T.V. for
exhausting valve

Display of opening time (s)

Display of closing time (s)

MANUAL TUNE FUNCTIONS

Access to the manual

TUNE functions can be obtained by the selecting of X.TUNE in the main menu

and briefly pressing the MANUAL/AUTOMATIC key or aborting the countdown by releasing the MANU-
AL/AUTOMATIC key.

The following parameters, which are determined automatically during

X.TUNE , may be preset or

changed afterwards manually.

TUNE-END

- Return to main menu

TUNE-POS

- Preset end positions

The

AUTOTUNE function determines the end positions of the control armature automatically on the

basis of the physical stops. Certain armatures (e.g. continuously turning butterfly valves) possess no
physical end stop, so that the end positions must be manually preset by means of

TUNE-POS. An

immediately following

AUTOTUNE takes over the manual end position settings and continues with

setting the positioning system and optimization of the positioner.

NOTE

If a manual preset of the end positions with

TUNE-POS is necessary, it must be done

before execution of AUTOTUNE.

5 s

Countdo

wn