Displays in the operating mode AUTOMATIC

With reference to the controller, the following displays are possible:

• Actual position of valve actuator

POS__XXX (0 ... 100 %)

• Position setpoint of valve actuator (perhaps rescaled by an

activated split-range function or correction characteristic)

CMD__XXX (0 ... 100 %)

• Input signal for position setpoint

INP__XXX (4 ... 20 mA)

By pressing the arrow keys, you can switch between these 3 display options.

If the device is in the safety position (for the relevant configuration, see menu item

BIN-IN),

the message

SAFE XXX appears on the display.

If the menu item

CUTOFF is activated and the process valve is in the tight-closing range, a

flashing

MIN or MAX symbol appears on the display.

NOTE

In the

AUTOMATIC mode, the normal controlled operation is executed and monitored.

Meaning of the keys in the operating mode AUTOMATIC

Operating mode AUTOMATIC (S/HART)

switch over the display

change the setpoint value:
with supplementary function

P.CONTRL / P.CO SETP / SETP INT

configured and display

SP set

or

or

> 3 s

No operating
action

AUTOMATIC
mode

MANUAL
mode

Release key

or

(> 5 Sek.)

Switch
display

Menu item

Configuration

END

POS__XXX

CMD__XXX

INP__XXX