70 - 8635
O
PERATING AND
C
ONTROLLER
F
UNCTIONS
X.LIMIT
Limitation of the mechanical stroke range
Factory setting:
LIM = 0%, LIM = 100%
This supplementary function limits the (physical) stroke to preset % values (minimum and maximum).
The range of the limited stroke is thereby set to 100 %. If the limited stroke range is left during operation,
negative or positive POS values or POS values greater than 100 % are displayed.
Entering the start value of the stroke range in %,
0..50% of the overall stroke
Entering the end value of the stroke range in %,
50..100% of the overall stroke
The minimum separation between
LIM and LIM
is 50 %.
XX
Setpoint [mA]
(INP)
limited
stroke
Limited
stroke [%]
(POS)
physical
stroke [%]
(POS)
unlimited
stroke
Control r
ange in
automatic mode
Correcting r
ange in man
ual mode
LIM XX
X-LIMIT
LIM XXX