S/hart) – Burkert Type 8635 User Manual

Page 27

Advertising
background image

8635 - 25

S

YSTEM

D

ESCRIPTION

(S/HART)

Analog repeat (optional)

4 ... 20 mA (electrically isolated)

Supply voltage

U

supply

= 12 ... 30 V DC

Burden

U

supply

≥ 12 V + RB • 20 mA

Binary outputs (optional)

to EN 50 227 (electrically isolated)

Supply voltage

5 ... 11 V DC

Current in switching status OPEN < 1.2 mA

Current in switch. status CLOSE

> 2.1 mA

Sense of action

NO (normally open) or NC (normally closed)

(may be parametrized)

max. permissible values

see Declaration of Conformity

PNEUMATIC DATA

Control medium

Quality classes to DIN ISO 8573-1

Dust content

Class 5:

max. 40 µm particle size

max. 10 mg/m³ particle density

Water content

Class 3:

max. pressure dew point

- 20 °C or at least 10 degrees below lowest

operating temperature

Oil content

Class 3: max. 1 mg/m³

Temperatur range of

- 25 ... + 65 °C (with non-Ex devices or T4/T5)

compressed air

- 25 ... + 60 °C (with T6)

Pressure range

1.4 ... 6.0 bar

Supply pressure

variation

max. ± 10 % during operation

Air flow capacity of control valve

at 1.4 bar pressure drop

over valve

ca. 55 L

N

/min STP for pressurizing and exhausting

at 6 bar pressure drop

over valve

ca. 170 L

N

/min STP for pressurizing and exhausting

Self-consumption of air

in balanced state

0.0 L

N

/min STP

Throttle screw

adjustment ratio ca.10:1

Connections

G1/4'' internal thread

Advertising