Factory settings of the process controller, Setting up a process control system, S/hart) – Burkert Type 8635 User Manual

Page 92

Advertising
background image

90 - 8635

O

PERATING THE

P

ROCESS

C

ONTROLLER

(S/HART)

Factory settings of the process controller

Function

Factory setting

P.CONTRL

P.CO DBND

1 %

P.CO PARA

KP

1.00

TN

999.9

TV

0.0

X0

0

P.CO SETP

SETP INT

P.CO FILT

0

P.CO SCAL

PV 000.0, PV 100.0

P.CO TUNE

D’ACT

➔ In all cases, first execute the self-parametrization for positioners

(X.TUNE).

➔ Add the supplementary function P.CONTRL to the main menu via the configuration

menu.

The function

P.Q’LIN is also added to the main menu with the function P.CONTRL.

➔ Call up the basic settings for the process controller under P.CONTRL.

Linearization of the process characteristic:

If you are dealing with a flow control system, the process characteristic can be linearized
automatically:

➔ Initiate the function P.Q’LIN.

Self-optimization of the process controller

➔ Activate the function P.CO TUNE and initiate the self-optimization of the PID parameters

of the process controller.

Setting up a process control system

In order to be able to operate the SIDE Control

(S/HART) as a process controller, you must execute the

following steps:

ATTENTION!

In all cases, keep to the following sequence: X.TUNE

P.Q’LIN P.CO TUNE