Error messages and malfunctions maintenance, S/hart) error messages on the lc display – Burkert Type 8635 User Manual

Page 140

Advertising
background image

138 - 8635

M

AINTENANCE AND

E

RROR

E

LIMIN

.

ON THE

P

ROCESS

C

ONTROLLER

(S/HART)

Error messages on the LC display

When operated according to these Operating Instructions

, the SIDE Control (S/HART) is

maintenance free.

Error messages and malfunctions

Maintenance

General error messages

Display

Causes of error

Remedy

INT.ERROR

Internal error

None, device faulty

PV FAULT

Signal error, actual value,

Check signal

process controller

Error messages on execution of the function X.TUNE

Display

Causes of error

Remedy

X.ERR 1

No compressed air connected

Connect compressed air

X.ERR 2

Air pressure failure during

AUTOTUNE

Check compressed air supply

X.ERR 3

Actuator or actuator system

None, device faulty

leaky on exhaust side

X.ERR 4

Actuator system leaky on

None, device faulty

pressurized side

X.ERR 5

The dead band of the internal position

Check alignment of the axle of the

sensor system is exceeded

SIDE Control

(S/HART) and

correct (see chapter

Installation)

X.ERR 6

The end positions for

POS-MIN and

Check whether the allocation of

POS-MAX are too near together.

the end positions to

POS-MIN and

POS-MAX via the function TUNE-
POS is correct.
If incorrect:
execute

TUNE-POS again.

If correct:
TUNE-POS with this arrangement
of the end positions is not possible
since they are too close together.

X.ERR 7

False allocation of

POS-MIN and

To determine

POS-MIN and

POS-MAX

POS-MAX, move the actuator in

each case in the direction shown
on the display.

Advertising