Hart, Hart) configuration, Display of the process variables – Burkert Type 8635 User Manual

Page 127

Advertising
background image

8635 - 125

O

PERATING VIA THE

HART

HAND TERMINAL

(HART)

Configuration

A prerequisite for configuration of the HART hand terminal is that the

AUTOTUNE function has been

executed before first commissioning.

First define the device-specific parameters such as instrument code, description, date, message or
factory number in the

Main menu under HART parameters -

device setup.

To configure the supplementary functions, enter the

Main menu / submenu Configuration

(Item 1).

As to be seen in the chapter

Operating and Controller Functions, all supplementary functions which you

want to use must be released.

For this purpose, enter the submenu

Configuration / Add Function (Item 2). With the operating key

select the corresponding function.

With the function key

F2 - ON, release the function if is was locked. You can equally lock a released

function again with the function key

F2 - OFF.

From item 3 of the submenu

Configuration on, you can alter the released supplementary functions.

Operating the positioner via the HART hand terminal

ATTENTION!

Display of the process variables

A display of the following process variables may be obtained via the menu

Main / Dynamic variables.

All parameters not altered by

AUTOTUNE are only stored in the RAM memory of the

SIDE Control and hence will no longer be present after a cold start. If you want to

permanently store the altered parameters, they must be saved via the menu item

EEPROM Control in the Main menu or in the menu Configuration -

Save to

EEPROM.

Variable

Description

Unit

POS

Actual position

%

POScurrent

Actual position

mA

INPcurrent

Input signal for setpoing position

mA

PV

Process value (irrelevant for positioner)

SP

Process setpoint (irrelevant for positioner)

Advertising